Citation

BibTex format

@article{Ariff:2016:10.1109/TPWRD.2016.2518080,
author = {Ariff, MAM and Pal, BC},
doi = {10.1109/TPWRD.2016.2518080},
journal = {IEEE Transactions on Power Delivery},
pages = {1815--1825},
title = {Adaptive Protection and Control in Power Systemfor Wide-Area Blackout Prevention},
url = {http://dx.doi.org/10.1109/TPWRD.2016.2518080},
volume = {31},
year = {2016}
}

RIS format (EndNote, RefMan)

TY  - JOUR
AB - This paper presents a new approach in adaptive outof-step(OOS) protection settings in power system in real-time.The proposed method uses extended equal area criterion (EEAC)to determine the critical clearing time (CCT) and critical clearingangle (CCA) of the system, which are vital information for OOSprotection setting calculation. The dynamic model parametersand the coherency groups of the system for EEAC analysis aredetermined in real time to ensure that the newly calculatedsettings suit with the prevalent system operating condition. Theeffectiveness of the method is demonstrated in a simulated datafrom 16-machine 68-bus system model.
AU - Ariff,MAM
AU - Pal,BC
DO - 10.1109/TPWRD.2016.2518080
EP - 1825
PY - 2016///
SN - 0885-8977
SP - 1815
TI - Adaptive Protection and Control in Power Systemfor Wide-Area Blackout Prevention
T2 - IEEE Transactions on Power Delivery
UR - http://dx.doi.org/10.1109/TPWRD.2016.2518080
UR - http://hdl.handle.net/10044/1/28868
VL - 31
ER -