Imperial College London

ProfessorGuillermoRein

Faculty of EngineeringDepartment of Mechanical Engineering

Professor of Fire Science
 
 
 
//

Contact

 

+44 (0)20 7594 7036g.rein Website CV

 
 
//

Assistant

 

Ms Eniko Jarecsni +44 (0)20 7594 7029

 
//

Location

 

614City and Guilds BuildingSouth Kensington Campus

//

Summary

 

Publications

Citation

BibTex format

@article{Vermesi:2018:10.3389/fbuil.2018.00044,
author = {Vermesi, I and Restuccia, F and Walker-Ravena, C and Rein, G},
doi = {10.3389/fbuil.2018.00044},
journal = {Frontiers in Built Environment},
pages = {1--8},
title = {Carbon monoxide diffusion through porous walls: evidence found in incidents and experimental studies},
url = {http://dx.doi.org/10.3389/fbuil.2018.00044},
volume = {4},
year = {2018}
}

RIS format (EndNote, RefMan)

TY  - JOUR
AB - It has been reported recently that carbon monoxide (CO) diffuses through gypsum board at a surprisingly high rate (Hampson et al., 2013). Because CO is poisonous and a by-product of systems typically present in residential housing such as boilers, generators and automobile engines, this finding could have a significant impact on the safety standards published by the National Fire Protection Association (NFPA) and International Code Council (ICC). In the USA, state legislation mandates the requirements for CO detection and warning equipment to be installed, but currently only enforces CO detection if there are communicating openings between the garage and occupied areas of a building. Therefore, there is a need to find out whether CO indeed diffuses through porous walls. In addition to investigating the validity of the experiments by Hampson (Hampson et al., 2013), this paper also collects a series of instances in the literature that show the diffusion of CO or other carbon-based gases. We have found a number of actual incidents and laboratory experiments which confirmed the transport of CO through other types of porous walls. We also found studies on the transport of other hydrocarbon gases with larger molecules than CO that can also diffuse through porous walls. We have also analyzed in detail the data from the recent experiments with a mass transfer model and confirm the validity of the findings for gypsum board. After 200 min, the CO concentration in the control chamber was around 200 ppm, which is high enough to affect people. Our analysis independently confirms that CO can diffuse through porous walls at a fast rate and that the phenomena merits further research for consideration in life safety standards.
AU - Vermesi,I
AU - Restuccia,F
AU - Walker-Ravena,C
AU - Rein,G
DO - 10.3389/fbuil.2018.00044
EP - 8
PY - 2018///
SN - 2297-3362
SP - 1
TI - Carbon monoxide diffusion through porous walls: evidence found in incidents and experimental studies
T2 - Frontiers in Built Environment
UR - http://dx.doi.org/10.3389/fbuil.2018.00044
UR - http://gateway.webofknowledge.com/gateway/Gateway.cgi?GWVersion=2&SrcApp=PARTNER_APP&SrcAuth=LinksAMR&KeyUT=WOS:000559215200001&DestLinkType=FullRecord&DestApp=ALL_WOS&UsrCustomerID=1ba7043ffcc86c417c072aa74d649202
UR - https://www.frontiersin.org/articles/10.3389/fbuil.2018.00044/full
UR - http://hdl.handle.net/10044/1/82830
VL - 4
ER -